Free Consultation
Engineered in Germany
ContactGet a Free Quote

EUROCODE 1 · EN 1991-1-3 + EN 1991-1-4

EN 1991 specifier tool

Pick your country and the wind / snow zone for the install site. The tool computes site reference wind pressure (qb) and characteristic snow load (sk) per Eurocode 1 national annexes, then checks each Luxa Sereno pergola against its rated envelope. For permit-level documentation always commission a site-specific structural calc.

Site loads & product compliance

Site reference wind pressure qb

0.391 kN/m²

vb,0 = 25 m/s

Site characteristic snow load sk

0.81 kN/m²

Productqb maxWind marginsk maxSnow marginVerdict
Luxa Sereno 7000.55+29%1.50+46%OK
Luxa Sereno 500M0.55+29%1.50+46%OK
Luxa Aperio 8000.50+22%1.20+32%OK

qb (kN/m²) = ½ × 1.25 × vb,0² · margin = (qbMax − siteQb) / qbMax · sk margin analogous.

METHOD

Wind reference pressure qb = ½ × ρ × vb,0² (ρ = 1.25 kg/m³). Site qb is the value at 10 m height, terrain category II (open, low vegetation). For taller installations or rougher / smoother terrain apply the cprob, ce(z) and orography correction factors per the relevant national annex.

Snow load on the structure s = μ1 × Ce × Ct × sk where μ1 (roof shape coefficient) = 0.8 for flat or low-pitch roofs < 30°, Ce = 1.0 for normal exposure, Ct = 1.0 unless heated. The Luxa Sereno tilt-louvre roof in closed position is treated as flat for snow drift calculations.

This tool returns characteristic / typical zone values. For permit submissions, your structural engineer must apply altitude correction (where sk depends on elevation), local exposure coefficients, and the partial safety factors of EN 1990 / national annex.